PNXH series arc suppression and elimination cabinet Back to the list
 

• major function

• Overvoltage protection function, limiting lightning overvoltage, operating over voltage and over voltage.

• replace the Petersen coil, eliminate the intermittent arc grounding fault, and has restricted the function of arc grounding overvoltage.

• judge grounding fault, distinguish the arc grounding, high resistance ground and metal grounding, and record the fault information, save the last 20 grounding fault information, the device falls never lost data.

• Can distinguish between single phase grounding and ferromagnetic resonance, fast elimination of PT ferromagnetic resonance.

• Alternative voltage transformer cabinets to provide voltage monitoring function.

• Line selection function: maximum 36 line selection function, fast and accurate detection of single phase to ground fault line.

• remote function: binary encoding (optional).

• High voltage current limiting fuse fusing alarm function.

• Communication function: the device can communicate with the host computer through the RS-232 or RS-485 communication port.
 

Device characteristics

 Comprehensive over-voltage protection function, all kinds of relative and phase and phase overvoltage are limited to low voltage level, the system insulation accidents can be greatly reduced, because the bus voltage is limited at the lower level, originally may lead to the ferroresonance over voltage possibility is greatly reduced.

 advanced scientific principle to eliminate arc and multiple means to ensure the arc grounding fault quickly eliminate, and arc over voltage is limited to low voltage level, the original according to the design specification requirements should be installed to eliminate arc coil system can no longer installed, and the limit voltage function will be over the installation of fire arc suppression coil is better and more perfect.

Two small resistance, fast, safe and reliable.

New line selection principle, accurate line selection.

According to the working principle of the device, it can be known that the arc suppression mechanism has nothing to do with the system grounding capacitance current, does not change the operation mode of the system, it is not necessary to consider the capacity increase, which is convenient for the reconstruction of the power network and the future planning.

Small footprint, saving system investment, can replace the PT cabinet, for the old station renovation only need to change the PT cabinet.

 multiple Petersen cabinet cabinet through coordination, bus communication, convenient for the user to find the fault line.

The whole device is integrated in a high voltage switch cabinet, which has the advantages of simple structure, small volume, convenient installation and low price, and has high performance price ratio compared with the arc suppression coil grounding system.

A high degree of automation, operation and maintenance is very convenient.

technical parameter

Rated frequency: 50 (Hz);

Rated voltage: 3, 6, 10, 35 (kV);

Rated current: 10, 31.5, 63, 80, 100, 125, 160, 200, 315, (A);

Rated short circuit breaking current: 50kA.

Intelligent controller parameters

Power supply voltage: DC/AC 220V, allow the deviation of -20% ~ 10%;

Power supply: <25W;

Communication interface: RS-485 (or RS-232);

> with line selection function, the maximum number of line 36 Road (determined according to user requirements);

> alarm and remote output contact capacity: AC250V 2A; DC220V 0.2A;

> Start > zero sequence voltage value 30V ~ 120V, action accuracy: the error is less than 5%;

> electromagnetic compatibility to achieve national level IV

 

 
PNXH series arc suppression and elimination cabinet
 
 

• The principle is advanced, the function is perfect, the automation degree is high.

• In the aspect of installation and maintenance, reliability and control function, it is more advantageous than arc suppression coil. • It is an ideal choice to solve the grounding problem of small grounding current system.

• The use of microcomputer control technology over voltage protection technology and vacuum high voltage switch and other components of a set of automatic protection system.

• in the neutral point non effective grounding power system, lightning and operation, resonance and arc grounding all of overvoltage limit;

• By limiting the fault recovery voltage and recovery voltage rise speed, rapid elimination of the intermittent arc grounding fault.

• The PT open triangular winding is adopted to eliminate the nonlinear resonance fault,

• With accurate grounding fault line selection and trip function, it can provide the basis for rapid fault location and fault exclusion, which greatly improve the safety and reliability of power supply.

• The principle is advanced, the function is perfect, the automation degree is high.

• In the aspect of installation and maintenance, reliability and control function, it is more advantageous than arc suppression coil. • It is an ideal choice to solve the grounding problem of small grounding current system.

• The use of microcomputer control technology over voltage protection technology and vacuum high voltage switch and other components of a set of automatic protection system.

• in the neutral point non effective grounding power system, lightning and operation, resonance and arc grounding all of overvoltage limit;

• By limiting the fault recovery voltage and recovery voltage rise speed, rapid elimination of the intermittent arc grounding fault.

• The PT open triangular winding is adopted to eliminate the nonlinear resonance fault,

• With accurate grounding fault line selection and trip function, it can provide the basis for rapid fault location and fault exclusion, which greatly improve the safety and reliability of power supply.

 
 
 